Wat één diploma daadwerkelijk bespaart: Het setpointbeleid dat de meeste kapitaalprojecten verslaat

Geschreven door

in

Wat één diploma daadwerkelijk bespaart: Het setpointbeleid dat de meeste kapitaalprojecten verslaat

Er is een energiemaatregel die niets kost, heeft geen aannemer nodig, betaalt de eerste verwarmingsrekening af en werkt in juli omgekeerd. It’s the thermostat. Every energy agency in Europe quotes some version of the same sentence: one degree off the setpoint saves around 6–7% of heating energy. The European Commission and the IEA say 7%. France’s environment agency ADEME says 7%. German heating analyses say 6%. The rule is real — but it’s an average of physics that ranges from 5% aan 20% depending on your building, your climate and your hours, and the same gesture in summer behaves differently. This article puts exact numbers on the rule, then shows where comfort law and human productivity quietly draw the line.

Where the number comes from

The one-degree rule appears in official sources with uncomfortable consistency:

  • De European Commission’s winter-preparedness guidance, restating the 2022 “Playing my part” campaign it ran with the IEA: “Lowering the temperature of your thermostat by 1 °C could save 7% of the energy used for heating” — worth up to €70 a year on a household bill, and the Commission notes the average EU home is heated above 22 °C.
  • ADEME, France’s ecological transition agency, in its official guide Réduire sa facture d’électricité: 1 °C less ≈ 7% less heating consumption; a properly programmed thermostat is worth up to 15% of heating energy.
  • German heating-cost analyses put it at Over 6% per kelvin of heating demand.
  • The building-physics reason it’s a range, not a constant: heat loss is proportional to the indoor–outdoor temperature difference, and degree-day statistics for Central Europe show a ~1.1 °C drop in winter mean indoor temperature roughly means a ~6% smaller heating season. Cold, leaky buildings respond better than the rule — simulation studies show 10–20% heating-demand cuts per 1 °C — while mild-climate, well-insulated buildings respond less, because their heating season is short.

So: 6% per degree is the right number to put in a policy memo. Anyone quoting 15% for a single degree is selling something.

What a degree is worth in euros

Percentages pay no invoices, so here is the euro version for a typical rented EU office, using Eurostat’s 2026 business energy prices (electricity €0.18/kWh; gas €0.0616/kWh, both EU averages for business bands). The table prices a 6% cut in useful heat demand per degree — the conservative central case.

Office (annual useful heat demand) Gas-heated: €/year per −1 °C Heat pump (SPF 3.4): €/year per −1 °C Electric resistance: €/year per −1 °C
Klein, 30,000 kWh (≈150 m² office) €123 €95 €324
Mid-size, 100,000 kWh (≈500 m²) €410 €318 €1,080
Large, 250,000 kWh (≈1,200 m²) €1,027 €794 €2,700

Three readings. Eerste, a single degree in a mid-size office is worth €410 a year — within a factor of two of what a complete LED lighting retrofit of that same floor would save, and it costs nothing to install. Tweede, the degree is worth more per kWh on direct electric heating, which is why ADEME prices it in euros for its electrified French households. Third, on a heat pump the degree still matters — it’s just worth roughly one-third as much, because the machine already buys three units of heat per unit of power.

Summer, in reverse: raising the cooling setpoint one degree saves at least the heating percentage, because fans and compressors shed two loads at once (sensible and latent). A Florida field verification of setback control in office spaces measured 24% cooling-energy reduction; a simulation study across all US climate zones found a one-degree summer raise plus optimal daily setbacks saved 6.8–37% of HVAC energy depending on size and climate. The working figure is 5–15% per degree raised.

Comfort: the bounds you’re allowed to work inside

A setpoint policy that makes people suffer gets reversed in a month, usually by the CEO’s own hand. The defensible bounds come from standards and law, not opinion:

  • EN 15251 / ASHRAE 55 define the comfort zone (ASHRAE’s is roughly 23–26 °C in summer, 20–23.5 °C in winter for seated work) and — crucially — allow it to move with clothing, air speed and expectations. Summer clothing is thinner; a 25 °C office in July is inside the standard, whatever December habits say.
  • Italy goes further and sets setpoints by law. Presidential Decree 74/2013 caps the winter weighted-average indoor temperature at 20 °C +2 °C tolerance (18 °C +2 for industrial buildings) and floors the summer temperature at 26 °C −2 °C — with limits on daily heating hours by climate zone. De 2022 energy-crisis decree tightened public buildings to 19 °C in winter and 27 °C in summer, and those habits largely stuck: Milan still runs radiators at 19 °C ±2, maximum 13 uren per dag. Italian offices have been living your “one degree lower” pilot for a decade.
  • Productivity data argues your current setpoint may be the expensive one. Multiple studies (summarised in the setpoint research above) find performance degrading above ~25 °C — which cuts against the office that freezes its IT department to save €400 and then wonders why output slumps.

The practical envelope: 20–21 °C heating, 25–26 °C cooling, is simultaneously within every European comfort standard, within Italy’s legal bounds, and two to three degrees cheaper than what most EU offices actually run.

Setback: one degree always-on, two degrees on a schedule

The always-on degree is the policy. The scheduled degrees — night and weekend setback — are where ADEME’s “up to 15%” comes from, and the US DOE’s rule of thumb quantifies it: Over 1% of HVAC energy per degree of setback held for eight hours. The catch is recovery physics: a heavy concrete building restarted Monday morning burns the savings back for two hours at full boiler output. Lightweight construction, radiant panels and a two-hour pre-heat ramp before arrival lose almost nothing to recovery. De 2023 MDPI buildings study is blunt on the upside: conventional fixed setback added 11.8% savings on top of occupancy reduction, en optimised setpoint-plus-setback selection across climates added another 34–38%.

A workable first policy, in one paragraph: occupied hours 20.5 °C heating / 25.5 °C cooling; unoccupied setback to 17 °C (heating) and weekend shutdown with Monday pre-heat; deadband wide enough that heating and cooling never fight; a single owner; override allowed but logged.

How to write the policy so it survives

1. Set the numbers from a measured baseline, not from this article: pull two years of degree-day-adjusted consumption, change the setpoint, and report the delta monthly. If your measured answer is 4% per degree, your building is mild-climate physics, not a broken boiler. 2. Put the legal bounds in writing (20 °C +2 / 26 °C −2 in Italy; EN 15251 elsewhere) so the debate is about compliance, not feelings. 3. Give floors a lever. Per-zone override within ±1 °C with automatic return-to-policy beats a thermostat war every time; one degree of variance is inside the comfort standard’s slack. 4. Pair with the summer sentence explicitly. The cooling degree is worth more per degree than the heating degree and needs no new equipment — only a July memo, and clothes guidance instead of a cardigan drawer. 5. Bank the money visibly. The €600 the one-degree policy saves buys a sub-meter, which finds the next €600.

One degree is not a sacrifice; on the evidence it’s the correct setpoint that cost-saving inertia never got around to claiming. Sign the memo.

Bronnen

—